REPLACE CRAC UNITS IN SERVER ROOM, BLDG 250, DAM NECK ANNEX
N4008524R2828
Department of the Navy, Navfacsyscom Mid-Atlantic. Commercial and Institutional Building Construction.
Response deadline
September 30, 2024 at 2:00 PM EDT
Closed 763 days ago. Posted September 25, 2024, first published August 29, 2024. Scheduled to archive October 15, 2024.
Get the next one like this from Department of the Navy by email, the day it is posted.Find my opportunities
This one closed in 2024
185 like it are open now in commercial and institutional building construction
- Sources Sought Notice/Market Research Project: Renovate SPS Phase 3
Department of Veterans Affairs, 246-Network Contracting Office 6
Sources soughtNAICS 236220Richmond, VA36C24627R0011Closes in 2 daysNov 4 - DSCR B34 & B42 System Smoke Testing & Hydro Jetting
Defense Logistics Agency, Dcso Richmond Division #1
Combined synopsis and solicitationSmall businessNAICS 236220Richmond, VASP470327Q0003Closes in 18 daysNov 20 - Renovation at Truman Hall Headquarters in Fort Belvoir, VA
Department of the Army, W072 Endist Louisville
Closes in 18 daysNov 20
All 185 open in commercial and institutional building construction
Description
As published on SAM.gov.
This project will provide for removal of two DX, nominal 26 ton air cooled split type Computer Room Air Conditioning (CRAC) systems. Each system consists of a Stulz model No. VFS–312–DAR-U indoor unit and SCS-312 remote air cooled condensing unit. The condensing units are located on the roof of B-250, which is a two story building. The associated refrigerant piping and ductwork shall also be removed.
Two new non-ducted, air cooled, split type CRAC systems configured for upflow air discharge, each sized for the indicated IT equipment heat dissipation and room envelope loads shall be provided. The intent is to provide a lead/lag arrangement and locate the new indoor units in the same approximate location as the existing units.
All building systems such as Architectural, Electrical, Fire Protection will be coordinated and modified to accommodate the mechanical renovation workThis project will provide for removal of two DX, nominal 26 ton air cooled split type Computer Room Air Conditioning (CRAC) systems. Each system consists of a Stulz model No. VFS–312–DAR-U indoor unit and SCS-312 remote air cooled condensing unit. The condensing units are located on the roof of B-250, which is a two story building.
The associated refrigerant piping and ductwork shall also be removed. Two new non-ducted, air cooled, split type CRAC systems configured for upflow air discharge, each sized for the indicated IT equipment heat dissipation and room envelope loads shall be provided. The intent is to provide a lead/lag arrangement and locate the new indoor units in the same approximate location as the existing units.
All building systems such as Architectural, Electrical, Fire Protection will be coordinated and modified to accommodate the mechanical renovation work. ONLY CONTRACTORS ON THIS MACC GROUP CAN SUBMIT A PROPOSAL.