Solicitation, total small business set-aside
A/C Installation Bahokas Peak Site
USCG-SPS-0002
US Coast Guard, Base Seattle. Plumbing, Heating, and Air-Conditioning Contractors.
Response deadline
July 31, 2024 at 4:00 PM EDT
Closed 778 days ago. Posted July 23, 2024, first published July 23, 2024. Scheduled to archive August 12, 2024.
Description
As published on SAM.gov.
DESCRIPTION: Installation of AC unit at Bahokas Peak Site to cool down sensitve equipment. Exact requirements listed below:
Furnish and install 2 each, 3-ton single zone, cooling only split AC units. Indoor unit shall be wall-mounted, powered from outdoor unit. Refrigerant type shall be R410A. Mfg/model shall be Daikin NV series or approved equal. Furnish and install pad and anchors for outdoor units. Provide wall openings for refrigerant lines and drain penetrations. Caulk seal watertight. Provide refrigerant lines between indoor and outdoor units.
Route condensate drain line from indoor units to the outside, and terminate to daylight at 6 inches above grade. Furnish and install circuit breakers (2x 20A, 208V, 1ph – field verify) to replace existing breakers and provide power to new AC units. Disconnect power from existing AC units and tag units “OOC, abandoned in-place”. Remove R22 refrigerant from both existing AC units and dispose in accordance with regulatory requirements.
For space temperature controls, set one indoor unit setpoint to 75 degrees F for normal space temperature control. Set the 2nd indoor unit to 80 degrees F for standby and runs automatically in the event of a load spike in the space. This notice is a combined synopsis/solicitation for a commercial products and commercial services in accordance with Federal Acquisition Regulation Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes a public solicitation. Please read this entire notice, the instructions herein, and the attachment documents carefully. This acquisition is on a Small Business Set-Aside only.
HOW TO RESPOND: To compete for this project, interested parties must be registered in SAM (System for Award Management) prior to close of this solicitation. https://www.sam.gov/portal/public/SAM/. The vendors SAM registration must be in an “ACTIVE” status prior to award. Vendors must ensure that the above listed NAICS codes are listed on their SAM registration to perform this type of service.
COST PROPOSALS: The contract will be awarded using simplified acquisition procedures in accordance with FAR part 13 and part 15 provide Firm Fixed-Price “broken out by labor hours, labor category, materials, and other direct costs”. Offerors must submit the proposal to Elizabeth Meister at elizabeth.a.meister@uscg.mil.
EVALUATION CRITERIA: The government will award a contract resulting from this request for quote (RFQ) to the responsible offeror whose offer conforming to the RFQ is the Lowest price Technically Acceptable (LPTA) quote. The lowest priced quote will be evaluated on technical acceptability, if it is found to be acceptable, an award will be made. If it is found to be unacceptable, the next lowest price will be evaluated. This process will continue until a technically acceptable offer is identified.
INQUIRIES: Telephone inquiries as described in the Statement of Work. Looking for a contractor to provide all personnel, equipment, transportation, tools, materials, supervision, and other items and services necessary for installation and testing of Air Conditioning unit. See attachments for SOW and additional information.
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
Points of contact
- Elizabeth Meisterelizabeth.a.meister@uscg.mil2062176145
Also open from this buyer
- Replace Building Boiler at USCG North Bend, ORCombined synopsis and solicitationSmall businessNAICS 238220North Bend, OR70Z033QSEAT0120Closes in 4 daysSep 21
- Repair Aircraft Hangar Apron Concrete - Air Station North BendCombined synopsis and solicitationSmall businessNAICS 237310North Bend, OR70Z033Q2027601Closes in 4 daysSep 21
- Base Seattle Fire Alarm Confidence TestingCombined synopsis and solicitationSmall businessNAICS 561621Seattle, WA70Z03326QSEAT32798Closes in 4 daysSep 21
- U.S. Coast Guard Air Station Port Angeles Main Gate Replacement - Amendment 01Combined synopsis and solicitationSmall businessNAICS 238990Port Angeles, WA70Z03326Q201900012Closes in 6 daysSep 23