Skip to content
Abierto

Award notice, total small business set-aside, first published as combined synopsis and solicitation

30 CES - Pad Mount Transformers (2 of 2)

FA461025Q0034

Department of the Air Force, FA4610 30 Cons PK. Power, Distribution, and Specialty Transformer Manufacturing.

Awarded

Govcrest Inc.

$251,224.00 obligated so far on USAspending

Description

As published on SAM.gov with the combined synopsis and solicitation of May 19, 2025.

**Reason for updated solicitation: UPDATED pricing sheet** Five (5) phase pad-mounted transformers shall have the following voltage ratings: •112.5 KVA, 208Y/120, 12 kV •150 KVA, 480Y/277, 12 kV •300 KVA, 480Y/277, 12 kV •500 KVA, 480Y/277, 12.47 kV •750 KVA, 480Y/277, 12 kV In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below:

•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available). •"Pentahead" cabinet locking mechanism/device. •Dead-Front construction (HV-200A load break elbows with shield adapters). •Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes - NEMA spades shall be provided per ANSI hole requirements. •Radial feed or Loop feed •Frequency: 60Hz. •Windings: HV/LV copper •Mineral Oil-filled (Non-PCB): Type FR-3 Fluid. •Standard impedance. •Mild steel high-voltage/low-voltage compartment barriers. •Cooling fins. •Proper grounding provisions. •Dial type gauges for oil temperature, liquid level and pressure/vacuum. •Bay-O-Net fuses & current-limiting fuses: properly sized - additionally, the transformer shouldbe equipped with three spare fuses. •Two-position "ON/OFF" load break primary switch •5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%) •Automatic pressure relief device mounted on the terminal compartment. •Oil drain valve with sampling device, and an oil-fill/oil-level plug. •Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate. •Compliant with 2016 DOE Efficiency Standard. •Four (4) lifting lugs. •Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish. •Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions. •Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.

The contract, on USAspending

Federal procurement data the awarding office reported to FPDS, matched to this solicitation by its number.

Recipient
Govcrest Inc.
UEI
NYL9YQK6WLM6
CAGE
9UCH5
Vendor location
Metairie, LA
Contract
FA461025P0059, purchase order
Obligated
$251,224.00
Actions
1 between June 27, 2025 and June 27, 2025
Competition
Competed Under SAP, 33 offers received
Set-aside reported
Small Business Set Aside - Total
Described as
30 Ces Pad Mount Transformers
Match
award number FA461025P0059 equals the contract number; same awarding office FA4610 (high confidence)

Publications

Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.

  1. May 14, 2025

    Combined synopsis and solicitation

    Due May 30, 2025 at 4:00 PM EDT. SAM.gov, notice 74550536d2304136af4583c6b8632821

  2. May 19, 2025

    Combined synopsis and solicitation

    Due May 30, 2025 at 4:00 PM EDT. SAM.gov, notice 1aaf7f7ea37c4fe49af0222053c8b2f7

  3. July 1, 2025

    Award notice, originally combined synopsis and solicitation

    Awarded to GOVCREST Inc. Metairie for $251,224. SAM.gov, notice 7409df6343f34b4482915fcd1d2c733b

Points of contact