Solicitation
MDF/Data Center Room-Based EXM/BDC
CTD_EXM_BDC
Administrative Office of the US Courts, Connecticut District Court. All Other Miscellaneous Electrical Equipment and Component Manufacturing.
Response deadline
August 16, 2024 at 5:00 PM EDT
Closed 811 days ago. Posted August 6, 2024, first published August 6, 2024. Scheduled to archive August 31, 2024.
Get the next one like this from Administrative Office of the US Courts by email, the day it is posted.Find my opportunities
This one closed in 2024
55 like it are open now in all other miscellaneous electrical equipment and component manufacturing
- CONVERTER, DIGITAL
Department of the Navy, NAVSUP Weapon Systems Support Mech
SolicitationNAICS 335999Anywhere in the USN0010427QUA02Closes todayNov 5 - CONVERTER,DIGITAL T
Department of the Navy, NAVSUP Weapon Systems Support Mech
SolicitationNAICS 335999Anywhere in the USN0010427QUA06Closes todayNov 5 - AMPLIFIER,AUDIO FRE
Department of the Navy, NAVSUP Weapon Systems Support Mech
SolicitationNAICS 335999Anywhere in the USN0010427RQA04Closes todayNov 5
All 55 open in all other miscellaneous electrical equipment and component manufacturing
Description
As published on SAM.gov.
1x ITEM A - One (1) 20kVA / 20kW Liebert EXM UPS (+1 Redundant), model 47SA020CBCM2 (refer to attached document for detailed specifications) System Input Voltage of 480V, 60Hz, 3 Phase, 3 wire plus ground.
System Output Voltage of 208/120V, 3 Phase, 4 wire plus ground · Fixed Capacity 20kVA UPS System · System includes One (1) 20kVA Redundant Power Module · 208V Native Output Voltage · Single Input Configuration · Transformer-Free Architecture - Efficiency up to 95% in double conversion mode · Unity Power Factor Rating - Delivers more usable power per kVA · Load Power Factor Support - Supports loads 0.5 lagging to unity without derating · Energy Optimization Mode (Eco-Mode) · 65kAIC Rating - Provides interrupting rating and labeling of 65kA · Active Power Factor Corrected IGBT Input Converter · PWM transistorized (IGBT) inverter · Continuous Duty Static Bypass Switch · Input Contacts - Dry contacts are available for functions including monitoring external breakers, on-generator signal, and other functions · Output Contacts - Dry contacts are available for functions including a permissive signal to maintenance bypass SKRU, to trip external breakers, and other functions · Generator Load Control - Suppresses battery charging reducing power demand by an external signal.
Shifts unit from Eco Mode to double conversion (if applicable), and synchronizes the inverter output with the bypass · Automatic retransfer - Provides return to inverter power after an overload · DSP based controls - Provides digital control of power conversion and system operation · Backlit LCD display - Monitors power conversion, UPS operation and utility conditions.
Deviations are logged for troubleshooting · Temperature-Compensated Charging/Battery Load Test · Top-and-bottom-entry cable access · Front only service access · Local Emergency Power Off (EPO) · LIFE™ Services for the 1st year · IP 20 enclosure · Casters and leveling feet · UL and cUL Listed to UL Standard 1778 5th Edition Additional Items Include:
· One (1) IntelliSlot Unity Dual Protocol Card;
P/N: IS-UNITY-DP; Monitoring and configuration of Vertiv products and environmental sensors through stand-alone Web UI or integration with Trellis™, Liebert Nform, LIFE™ Services. Supports third-party management systems using SNMP, Modbus or BACnet. · One (1) IS-RELAY Relay Contact Card Battery System, Internal to UPS Cabinet Includes:
· 22 Minutes at 20kW Load (Approximately 65 Minutes at 8kW load) · One (1) Internal String of Enersys HX205-FR Batteries 1x ITEM B - One (1) Liebert EXM Maintenance Bypass Cabinet, model 47MBE37AC3R1 (refer to attached document for specifications) · 3 Switching Devices (BIB,MBB,MIB) · Key Interlock (SKRU) · Cabinet Mounted Right Attached to UPS Cabinet with connecting cables factory supplied · 600 MM - 23.6 inches Frame Size · 480V/ 208V Input Transformer Included · Front Access service design · One (1) 225 Amp, 54 pole SqD bolt/plug-in panelboard 1x ITEM C – Vertiv Standard Factory Testing w/ Certified Test Reports 1x ITEM D – Start Up Service by Vertiv Customer Engineer – 7x24 Mandatory Service Inclusion: **Quote must include delivery inside rigging services to the 7th floor.
Loading dock and freight elevator are available. **Quote must include rigging removal services and disposal of three existing Liebert chassis on the 7th floor room. Units will be disconnected, and battery packs will be reduced to a safe 12v potential by on-site electrician prior to delivery of Item A and Item B above. We are with the Federal Government and tax exempt.
Shipping Address: Jeff Gerace Room 746, Clerk’s Office 450 Main Street Hartford, CT 06103