Combined synopsis and solicitation

Dry Chemical HAZMAT Locker System Replacement at U.S. Coast Guard Sector San Diego

37250PR250000236

US Coast Guard, Base Los Angeles/Long Beach. Prefabricated Metal Building and Component Manufacturing.

Response deadline

September 16, 2025 at 9:00 AM EDT

Closed 411 days ago. Posted September 9, 2025, first published September 2, 2025. Scheduled to archive October 1, 2025.

Get the next one like this from US Coast Guard by email, the day it is posted.Find my opportunities

This one closed in 2025

7 like it are open now in prefabricated metal building and component manufacturing

All 7 open in prefabricated metal building and component manufacturing

Description

As published on SAM.gov.

Replace and Install 06 Hazmat Locker Systems at US Coast Guard Sector San Diego:

2710 North Harbor Drive
San Diego CA 92101

Industry Day Site Visit will be held: Friday, September 12th @0900

Please contact Kyle Kagami, Facilities Engineer Cell: (832) 293-5117 for visitor passes

Replacement of the (6) dry chemical hazmat locker systems. Current systems are no longer supported and have multiple deficiencies.


Remove the system release, cylinder, supply line, nozzle, pull station and pressure switch at each hazmat room.
Install Pyrochem MONARCH dry chemical system components at each hazmat room:
1. MCH3 mechanical release and CO2 actuation cartridge w/MB-2 mounting bracket.
2. PCL-17ABC cylinder w/MB-15 mounting bracket.
3. Explosion proof pressure switch.
4. 3/4" galvanized supply line pipe and a NV-ABC nozzle.
5. RPS-M remote pull station.
6. Update existing mechanical detection.


All necessary Bracketing and Supports per the Monarch Manual.
Qualifications:
Devices such as contactors, shunt trips, solenoids, fans, relays, controls, power, line voltage or building fire alarm tie-in if applicable is by others. Wiring from Monarch micro switches to said devices by others.


Add: for one (1) suppression plan and NICET III stamp comprised of all six (6) systems. Individual suppression plans for
each system to incur additional charges. Permit/plan review fees if assessed to be reimbursed at cost.
Add: per system for explosion proof pressure switches, in lieu of micro switches, for electrical interlocks.

Installation to be performed during normal business hours 7am-3:30pm.
Electrical connection safe-off and reconnection by others.
There are existing penetrations in the cabinets housing the suppression systems. Sealing of the penetration's by others.
Services to be completed


[Industrial/Dry Chemical Suppression] Location - Building
DEFICIENCIES (SYSTEMS ARE NO LONGER SUPPORTED, DUE TO THE TYPE AND QUANTITY OF DEFICINCIES,
REPLACEMENT MATERIAL IS NOT AVAILABLE TO CERTIFY SYSTEMS. PROPOSED RESOLUTION IS REPLACEMENT OF
SYSTEMS WITH A PRODUCT LINE CURRENTLY SUPPORTED)
BLDG 66509:
-PULL STATION SEIZED
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED

BLDG 66510:
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66511:
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66512:
-PRESSURE SWITCH WOULD NOT RESET (WATER DAMAGE)
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66513:
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66514:
-CYLINDER LOW ON PRESSURE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED

Publications

Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.

  1. September 2, 2025

    Combined synopsis and solicitation

    Due September 16, 2025 at 9:00 AM EDT. SAM.gov, notice 3ae106e7df854c32a7fad4220ef2e876

    3 revisions on SAM
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 2, 2025: publish, combined synopsis and solicitation
  2. September 9, 2025

    Combined synopsis and solicitation

    Due September 16, 2025 at 9:00 AM EDT. SAM.gov, notice 18a996150e484a8dab5a70ddbc6e0d9f

    3 revisions on SAM
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 2, 2025: publish, combined synopsis and solicitation
  3. September 9, 2025

    Combined synopsis and solicitation

    Due September 16, 2025 at 9:00 AM EDT. SAM.gov, notice 8097392341b94b6092fdc4203a18d976

    3 revisions on SAM
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 9, 2025: publish, combined synopsis and solicitation
    • September 2, 2025: publish, combined synopsis and solicitation

Points of contact