Skip to content
Abierto

Combined synopsis and solicitation

Building 65 Switch 1 Repair at VAMC Central Western MA

36C24126Q0671

Department of Veterans Affairs, 241-Network Contract Office 01. Electrical Contractors and Other Wiring Installation Contractors.

Awarded

True Circuit Electrical Testing L.L.C.

$34,585.00 obligated so far on USAspending

Description

As published on SAM.gov.

AMENDMENT NO. 2 SOLICITATION NO. 36C24126Q0671 DATE: 8/3/2026 This amendment is issued to inform all interested vendors of the following changes to the solicitation:

1. Inclusion of Electrical One-Line Diagram The solicitation is updated to include the attached medium-voltage electrical one-line diagram (Campus Electrical online working copy.pdf 12.23.25), which provides a comprehensive overview of the site s electrical distribution system. Vendors are advised to review this diagram for details on system configuration, isolation points, and load connections.

2. Responses to Request for Information (RFI): Switch 1 s Upstream Source, Isolation Points, and Downstream Loads: Please see the attached Switch 1 diagram for its upstream source and isolation points. Downstream loads include B65 breaker, SW2, and TR15 (1500KVA 13.8KV TO 480/277V).

Alternate, Emergency, or Potential Backfeed Sources: Building 15 (B15) is equipped with an Automatic Transfer Switch (ATS) and generator, providing emergency and alternate power sources. Responsibility for Operating Upstream Medium-Voltage Equipment (Switching, LOTO, Grounding, Restoration): As stated in the Statement of Work (SOW), the contractor is responsible for all switching and Lockout/Tagout (LOTO) procedures, including grounding and restoration of upstream medium-voltage equipment. VA personnel will not perform these operations.

Arc-Flash Information, Protective-Device Settings, and Outage Impact: All arc-flash values, protective-device settings, and outage-impact details must be verified in the field. For planning purposes, assume arc-flash values are less than or equal to 40 Cal/cm².

VA Electrical-Shop Support During Shutdown: VA electrical-shop support will not be available during the shutdown.

3. Extension for Due Date of Quotes The due date for the submission of quotes has been extended.

New Due Date:

August 5, 2026 Time: 4:00 PM EST 4. All other terms and conditions of the solicitation remain unchanged. Vendors are reminded to review all aspects of the solicitation and consider this amendment when preparing their responses.

The contract, on USAspending

Federal procurement data the awarding office reported to FPDS, matched to this solicitation by its number.

UEI
J3E4ENF28YB5
CAGE
9SHG0
Vendor location
Manalapan, NJ
Contract
36C24126P0629, purchase order
Obligated
$34,585.00
Actions
1 between September 1, 2026 and September 1, 2026
Competition
Competed Under SAP, 5 offers received
Set-aside reported
No Set Aside Used.
Described as
Electrical Switch Repair
Match
solicitation number 36C24126Q0671 equals the FPDS solicitation identifier; same awarding office 36C241 (high confidence)

Publications

Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.

  1. July 20, 2026

    Combined synopsis and solicitation

    VAMC Central Western MA Bldg. 65 Electrical Switch Repair

    Due August 3, 2026 at 4:00 PM EDT. SAM.gov, notice a60a6ff1c3624b0b80ab6929443fa014

  2. July 27, 2026

    Combined synopsis and solicitation

    Building 65 Electrical Switch 1 Repair

    Due August 3, 2026 at 4:00 PM EDT. SAM.gov, notice 77b56737e0904a8e828ef80d3ef135cf

  3. August 3, 2026

    Combined synopsis and solicitation

    Due August 5, 2026 at 4:00 PM EDT. SAM.gov, notice f64d910079894af99b36d8953c9665ca

Points of contact