Consolidation or bundling
FUEL TANK INTEGRITY TESTING
31125PR260000720
US Coast Guard, Base Cape Cod. All Other Professional, Scientific, and Technical Services.
Status
Archived
Posted June 11, 2026. Scheduled to archive July 11, 2026.
Get the next one like this from US Coast Guard by email, the day it is posted.Find my opportunities
This one is not taking offers
26 like it are open now in all other professional, scientific, and technical services
- Data & AI Mission Expert Services (DAMES) IDIQ
Department of the Air Force, FA7014 Afdw PK
Sources soughtNAICS 541990Andrews AFB, MDFA701427SAFCNDAMESCloses tomorrowNov 2 - FIRE FIGHTING EQUIPMENT INSCPECTIONS
Department of the Navy, NAVSUP FLT Log CTR Norfolk
Sources soughtNAICS 541990Virginia Beach, VA1301428425Closes tomorrowNov 2 - 711th HPW Mission Support Services MAC IDIQ
Department of the Air Force, FA2396 USAF AFMC AFRL PZL AFRL Pzle
Combined synopsis and solicitation8(a)NAICS 541990Wright-Patterson AFB, OHFA239626RB008Closes in 2 daysNov 3
All 26 open in all other professional, scientific, and technical services
Description
As published on SAM.gov.
1.1 SCOPE: The Contractor shall provide all personnel, equipment, tools, materials, supervision, and other items and services necessary to perform external inspections of aboveground fuel tanks, and potassium sodium tanks. Internal inspections and tank wall thickness measurements shall be included in inspection for three (3) tanks – one (1) 30,000 gallon JP-8 tank, and two (2) 15,000 gallon JP-8 tanks located adjacent to taxiway delta. Contractor shall provide a detailed report of conditions found to include estimates for repairs. All work located at USCG Base Cape Cod in Bourne, MA 02542.
1.1.2 REQUIRED WORK: This list should not be considered complete. It represents the general items needed to complete the contract requirements. Base Cape Cod manages six (6) above ground tanks that are greater than or equal to 6,000 gallons, that are used for the storage of fuel products. Three (3) above ground tanks, used for the storage of gasoline, are located adjacent to Coast Guard Base Cape Cod’s (BCC) Mini Mart. Two (2) of the tanks adjacent to BCC’s Mini-Mart have a 10,000 gallon capacity the third tank has a 6,000 gallon capacity. Three (3) above ground tanks, used to store JP-8 (aviation fuel), are located adjacent to Taxiway Delta behind building 3170. Two (2) of the tanks adjacent to Taxiway Delta have a 15,000 gallon capacity, the third tank has 30,000 gallon capacity. Base Cape Cod also manages two 5,000 gallon potassium sodium tanks located behind building 124. Inspect the tanks in accordance with Steel Tank Institute (STI) SP001 and complete the STI SP001 AST record. Perform wall thickness testing, and internal inspection IAW API 653. Wall thickness testing, and internal inspection to only be completed on 30,000-gallon tank, and two (2) 15,000-gallon tanks located adjacent to taxiway delta. Drafting a report on the condition of the tanks including any observed deterioration, the results of tests, and predictions of the expected service life remaining.
1.1.3 TANK INSPECTION SCHEDULE: Work shall be completed over a four (4) year period. Year 1; Inspect 30,000 gallon tank adjacent to taxiway delta Year 2, Inspect two (2) 15,000 gallon tanks adjacent to taxiway delta Year 3, Inspect two (2) 10,000 gallon tank adjacent to CGEX Year 4, Inspect 5,000 gallon tank adjunct to CGEX & (2) 5,000 gallon Potassium Sodium Tanks
SEE SOW FOR FULL DETAILS
Attachments
Files listed on SAM.gov. The ones we hold a copy of download from here; the rest open SAM's download, which needs no account.
- Tank Integrity Testing Statement of Work.doc137 KB, June 11, 2026
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
June 11, 2026
Consolidation or bundling
SAM.gov, notice ce31cc1ec36641bdbd8a9e494aa296e6
1 revisions on SAM
- June 11, 2026: publish, consolidation or bundling
Points of contact
- STEVE SIMPSONSTEVEN.M.SIMPSON@USCG.MIL2076102315
- SCOTT AMIRAULTSCOTT.F.AMIRAULT@USCG.MIL5089686502