Sources sought, total small business set-aside
PND 08-30-2026 - Actionable - 436- Audiometric Sound booth (VA-26-00067708)
36C25926Q0508
Department of Veterans Affairs, Network Contract Office 19. Electromedical and Electrotherapeutic Apparatus Manufacturing.
Response deadline
June 24, 2026 at 2:00 PM EDT
Closed 84 days ago. Posted June 17, 2026, first published June 17, 2026. Scheduled to archive August 23, 2026.
Description
As published on SAM.gov.
Description and Salient Characteristics Audiometric Sound Booth Description: The VA is seeking one (1) custom-built audiometric sound booth for the newly built Kalispell, Montana Community-Based Outpatient Clinic (CBOC), 750 Reserve Pl. Kalispell, MT. 59901 Room 124. This requirement will cover the procurement, delivery, installation, and initial testing/calibration of one audiometric sound booth. The sound booth must integrate with existing audiology equipment and meet current accessibility, acoustic, and infection control requirements. Contractor shall assemble and install the sound booth at the designated clinic location. Installation must include:
*Offloading of all materials *Placement of booth per floor plan *Onsite assembly (modular, as required for building entry) *Mechanical and electrical hookup to VA infrastructure *Ensuring full ADA accessibility *Ensuring booth interfaces with existing clinic audiometers, including power/cable pass- throughs and support for networked devices if specified. *Ensuring to perform and document initial certification of booth ambient noise levels in compliance with ANSI S3.1 standards and provide written report of results. *Providing onsite (or virtual, if required by VA) training for VA staff in use and basic maintenance of the booth and provide user manuals and warranty documents.
The VA will provide: Existing audiometers and network cabling for booth integration Site drawings and floor plans for booth placement Access to electrical and HVAC as required Facility access and escort as needed SALIENT CHARACTERISTICS: AUDIOMETRIC SOUND BOOTH Size and Dimensions Interior dimensions suitable for patient comfort and wheelchair accessibility Sound Booth door clear opening width minimum 32 inches to accommodate mobility devices.
Inside Dimensions Must Not Exceed: 68" Width x 68" Length x 78" Height Outside Dimensions Must Not Exceed: 76" Width x 76" Length x 91" Height Sound Booth should be Low Profile 1 5/16" Floor (Standard) Opening of Sound Booth door should be at least 36 wide. Acoustic Performance Booth must meet ANSI S3.1 or ANSI S3.2 standards for permissible ambient noise levels for audiometric testing. Noise reduction rating (NRR): Must provide minimum 60 dB attenuation.
Walls and ceilings must be constructed to block external environmental noise and vibration. Accessibility Compliant with ADA standards: Level entry, non-skid thresholds, and sufficient turn radius inside booth. Door hardware must be easy to operate by individuals with disabilities. Electrical and Lighting Booth must include interior lighting, minimum 400 lux, flicker-free. Electrical outlets: Minimum one duplex outlet. Cable pass-through ports for audiometer and other equipment.
Ventilation Non-noise (silent) ventilation system to avoid interference with testing. Air exchange rate to ensure comfort for patient and provider. Materials and Construction Durable, non-toxic materials. Easy-to-clean surfaces, impervious to liquids and disinfectants. Fire-retardant construction (meet appropriate fire safety codes). Warranty and Service Minimum one-year manufacturer s warranty on booth and components. On-site installation and calibration included. Technical support and manuals provided. Installation Contractor shall assemble and install the sound booth at the designated clinic location. Installation must include:
*Placement of booth per floor plan *Onsite assembly (modular, as required for building entry) *Mechanical and electrical hookup to VA infrastructure *Ensuring full ADA accessibility Vendor must provide delivery, assembly, and installation, including site-specific customization as needed. Must fit through standard VA facility doors or be modular for assembly on-site. Equipment Compatibility Must be able to interface with VA-provided audiometers and hearing test equipment (list compatibility requirements if possible). Certification and Compliance Must provide documentation of ANSI and ADA compliance. Vendor must comply with VA security and facility access requirements. END DOCUMENT
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
June 17, 2026
Sources sought
Due June 24, 2026 at 2:00 PM EDT. SAM.gov, notice 5052a5368e774b9ba4dc9ba9e33c53c1
June 17, 2026
Sources sought
Due June 24, 2026 at 2:00 PM EDT. SAM.gov, notice aba592c2fda84b69a087be67a6d398b2
June 17, 2026
Sources sought
Due June 24, 2026 at 2:00 PM EDT. SAM.gov, notice e68230d95dfd47b3948c23a8f46a50fe
Points of contact
- Barron Long, Contracting Officerbarron.long@va.gov303-712-5741
Also open from this buyer
- EksoNR Exoskeleton – Gait Training DeviceCombined synopsis and solicitationSmall businessNAICS 334510Oklahoma City, OK36C25926Q0851Closes tomorrowSep 17
- Bulk Oxygen and Tank Rental for Oklahoma City VA Health Care System Base Plus 4 Option YearsCombined synopsis and solicitationSDVOSBNAICS 325120Oklahoma City, OK36C25926Q0814Closes tomorrowSep 17
- 635-21-139 | Repair Parking Garage 1 Deficiencies | CON (VA-26-00041470) (NRM - SCIP# VHA19-635-2023-52398)SolicitationSDVOSBNAICS 236220Oklahoma City, OK36C25926R0082_1Closes tomorrowSep 17
- CCTV MOBILE CAMERA TRAILERS - SHERIDAN VAMCCombined synopsis and solicitationSmall businessNAICS 561621Greenwood Village, CO36C25926Q0812Closes tomorrowSep 17
- Surgery Lumber Retractor Instruments – Domestic End ProductsCombined synopsis and solicitationSmall businessNAICS 339112Muskogee, OK36C25926Q0861Closes tomorrowSep 17