Combined synopsis and solicitation, total small business set-aside
30 CES - Pad Mount Transformers (1 of 2)
FA461025Q0041
Department of the Air Force, FA4610 30 Cons PK. Power, Distribution, and Specialty Transformer Manufacturing.
Response deadline
May 30, 2025 at 4:00 PM EDT
Closed 476 days ago. Posted May 14, 2025. Scheduled to archive June 14, 2025.
Description
As published on SAM.gov.
Funds are not presently available for this contract. The Government’s obligation under this contract is contingent upon the availability of appropriated funds from which payment for contract purposes can be made. No legal liability on the part of the Government for any payment may arise until funds are made available to the Contracting Officer for this contract and until the Contractor receives notice of such availability, to be confirmed in writing by the Contracting Officer.
Five (5) phase pad-mounted transformers shall have the following voltage ratings: •112.5 KVA, 208Y/120, 12 kV •150 KVA, 480Y/277, 12 kV •300 KVA, 480Y/277, 12 kV •500 KVA, 480Y/277, 12.47 kV •750 KVA, 480Y/277, 12 kV In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below:
•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available). •"Pentahead" cabinet locking mechanism/device. •Dead-Front construction (HV-200A load break elbows with shield adapters). •Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes - NEMA spades shall be provided per ANSI hole requirements. •Radial feed or Loop feed •Frequency: 60Hz. •Windings: HV/LV copper •Mineral Oil-filled (Non-PCB): Type FR-3 Fluid. •Standard impedance. •Mild steel high-voltage/low-voltage compartment barriers. •Cooling fins. •Proper grounding provisions. •Dial type gauges for oil temperature, liquid level and pressure/vacuum. •Bay-O-Net fuses & current-limiting fuses: properly sized - additionally, the transformer shouldbe equipped with three spare fuses. •Two-position "ON/OFF" load break primary switch •5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%) •Automatic pressure relief device mounted on the terminal compartment. •Oil drain valve with sampling device, and an oil-fill/oil-level plug. •Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate. •Compliant with 2016 DOE Efficiency Standard. •Four (4) lifting lugs. •Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish. •Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions. •Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
May 14, 2025
Combined synopsis and solicitation
Due May 30, 2025 at 4:00 PM EDT. SAM.gov, notice 4165a3fd1e15480aaa9a985e47206ccd
Points of contact
- SrA Christopher Mendozachristopher.mendoza.17@spaceforce.mil8056061507
- TSgt Mark Wheelermark.wheeler.10@spaceforce.mil
Also open from this buyer
- Commercial Internet Services for Unaccompanied Housing (UH) DormitoriesCombined synopsis and solicitationSmall businessNAICS 517111Lompoc, CAFA461026Q0049Closes todaySep 18
- Integrated Solid Waste ManagementCombined synopsis and solicitationSmall businessNAICS 562111Lompoc, CAFA461026Q0030Closes in 3 daysSep 21
- VSFB Chapel Music ServicesSolicitationNAICS 711130Lompoc, CAFA461026Q0056Closes in 4 daysSep 22
- Titian Dorm Beds and MattressCombined synopsis and solicitationSmall businessNAICS 337122Lompoc, CAFA461026Q0055Closes in 5 daysSep 23
- VSFB Heavy Equipment Recovery and TransportationCombined synopsis and solicitationSmall businessNAICS 488410CaliforniaFA461026Q0053Closes in 5 daysSep 23