Special notice, service-disabled veteran-owned small business sole source, first published as solicitation
Walk-In Refrigerator
36C24W25Q0218
Department of Veterans Affairs, Rpo West. Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing.
Awarded
$85,850.00 obligated so far on USAspending
Description
As published on SAM.gov.
NOTICE FOR REQUEST FOR QUOTE AMENDMENT SOLICITATION NUMBER:
36C24W05Q0218 AMENDMENT NUMBER:
0001 DATE:
July 10, 2025 PROJECT NUMBER:
N/A PROJECT TITLE:
Walk-in Refrigerator LOCATION: VA Medical Center, Tulsa, OK, 74127 REASON FOR AMENDMENT: Answer Questions 1 – 13, Condensing Unit Type – Missing Division
AMENDMENT:
0001 Question:
1 - Condensing Unit Type: I see both air-cooled and water-cooled listed in the RFQ and specifications.
VA Response: An air-cooled type condensing unit is required.
Question:
2 - Condensing Unit Location: Can you find out where the condensing units are located and I need to know the total horizontal and vertical feet of pipe too.
VA Response: The condensing unit will be mounted above the ceiling on top of the cooler. The precise location will have to be determined by the contractor base on access, and position of other MEP (mechanical, electrical, piping) in the space.
Question: 3 - Chamber temperature set point: Can you confirm if this is a 2-8C° Cold Room.
VA Response: The set point will be 2 degrees Celsius.
Question: 4 - Temperature uniformity: Is this required for this type of “Lab Grade Chamber”? I typically +/-2.0°C volumetric temperature uniformity in Pharma applications.
VA Response: Correct, volumetric temperature uniformity should be +/- 2 degrees Celsius.
Question:
5 - Relative Humidity and Uniformity: Neither of these are listed.
VA Response: I am unaware of any humidity uniformity requirement.
Question:
6 - 100% Mechanical Redundancy: Are they looking for an “A” and “B” systems that are identical to each other for system switchover? Or are they looking for dual circuited evaporators with redundant condensing units?
VA Response: The exact solution is up to your discretion. The only requirement that we have is 100% redundancy for the compressor.
Question:
7 - Labor: Would this be a Prevailing Wage Job?
VA Response: Yes, local labor would apply because there are labor qualifications specified.
Question:
8 - Freight Elevator and Size: Is one available and can we get the size.
VA Response: 69” W x 102” D x 102”H Door opening 54” W x 96”H Question:
9 - Building Drawings: Are these available?
VA Response: Drawings will be made available to all vendors that attend the site walk-through.
Question:
10 - Loading Dock: Is a loading dock available?
VA Response: The loading dock can be made available for scheduled loading and unloading. The delivery time and location can be worked out post award.
Question:
11 - Condensing Unit Voltage: Will this be 208/230V or 460V?
VA Response: 208v.
Question:
12 - Chamber Interior Finish: Would this be 304 stainless steel walls floors and ceilings?
VA Response: Stainless steel is the required surface for all visible surfaces, including floors, walls and ceilings.
Question:
13 - Missing Divisions:
VA Response: All VA Master Construction Specifications can be obtained here: https://vatilms.va.gov/vatilms/reports/PG-18-1 Please give it a minute to load and click “VA Specs”. THE DUE DATE FOR OFFERS REMAINS AUGUST 12, 2025 @ 12:00PM.
All other terms and conditions remain unchanged.
The contract, on USAspending
Federal procurement data the awarding office reported to FPDS, matched to this solicitation by its number.
- Recipient
- Ce Solution Plus Corp.
- UEI
- ZVQVJUVMF9K6
- CAGE
- 9KV33
- Vendor location
- Astoria, NY
- Contract
- 36C24W25P0193, purchase order
- Obligated
- $85,850.00
- Actions
- 3 between September 18, 2025 and June 1, 2026
- Competition
- Competed Under SAP, 2 offers received
- Set-aside reported
- Small Business Set Aside - Partial
- Described as
- Walk-In Laboratory Refrigerator
- Match
- solicitation number 36C24W25Q0218 equals the FPDS solicitation identifier; same awarding office 36C24W (high confidence)
- Record
- USAspending award page
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
Points of contact
- Robert M. Clark Jrrobert.clark15@va.gov2546614699
Also open from this buyer
- Corneal Analyzer OPD-Scan III Wavefront AberrometerSources soughtNAICS 339115San Francisco, CA36C24W26Q0234Closes in 3 daysSep 20
- Ponce Vet Center RelocationSources soughtSmall businessNAICS 531120Ponce, PR36C24W26Q0254Closes in 3 daysSep 20
- Vet Center in Helena MTSolicitationNAICS 5311Helena, MT36C24W26R0075Closes in 3 daysSep 20
- EVERETT VET CENTER SUCCEEDING LEASESources soughtSmall businessNAICS 531120Washington36C24W26Q0261Closes in 4 daysSep 21
- Everett Vet Center RelocationSources soughtSmall businessNAICS 531120Washington36C24W26Q0257Closes in 4 daysSep 21