# Chemical Storage Building

Canonical: https://abierto.us/opportunities/w911s226u3863

- Solicitation number: W911S226U3863
- Notice type: Combined synopsis and solicitation
- Status: Closed. Deadline was August 27, 2026 at 2:00 PM EDT
- Department: Department of the Army
- Agency: Department of the Army
- Contracting office: W6QM Micc-Ft Drum (W911S2)
- NAICS: 332311 Prefabricated Metal Building and Component Manufacturing
- Product or service code: 5670 Building Components, Prefabricated
- Set-aside: Total small business set-aside
- First posted: July 29, 2026
- Last posted: August 24, 2026
- SAM.gov: https://sam.gov/workspace/contract/opp/5895ed8ef5244952aaeec88d443ef15a/view

## Description

The chemical storage building must meet several specifications for construction, safety, and utility. The required minimum dimensions are 42 feet in length, 8 feet in width, and 8 feet 3 inches in height. Access shall be provided by a 60-inch by 80-inch set of double doors, with at least one 36-inch active leaf, centered on one of the 42-foot walls and secured with a padlock-compatible handle.

For spill containment, the building must include a sump with a minimum capacity of 1200 gallons.The structure must feature a robust fire-rated design, with walls tested by Intertek for a minimum 4-hour rating and a roof tested for a minimum 3-hour rating.

Electrical specifications include a 12-space, 100-amp NEMA 3R main breaker panel (120V/240V), two Class 1, Division 2 explosion-proof LED light fixtures with a switch for the interior, and a dust/vapor-resistant exterior light with a photocell installed outside the hazard zone.

Ventilation will be handled by an explosion-proof exhaust system rated for 335 CFM or higher, suitable for petroleum-based storage and compliant with all NFPA/UFC codes, complete with an indicator light and an emergency shut-off switch.For safety and functionality, the building shall be equipped with a grounding kit including an 8-foot ground rod, 10 feet of cable, and a clamp. The interior will be furnished with three-tier, 5-foot-long shelves that are 14 inches deep with a 2-inch lip.

A non-perforated, skid-resistant steel ramp, measuring at least 52 inches wide by 72 inches long, must be included. Additionally, the unit shall come with three 10-pound ABC dry chemical fire extinguishers: two installed inside on either side of the door, and one mounted outside in a weatherproof cabinet. The completed chemical storage building is to be delivered to Building P-91, Railroad Street, Fort Drum, NY 13602.

## Publications

- July 29, 2026: Combined synopsis and solicitation, due August 7, 2026 at 2:00 PM EDT. Notice 0febcf070c9c4610975f7b50057f55a5. https://sam.gov/workspace/contract/opp/0febcf070c9c4610975f7b50057f55a5/view
- August 24, 2026: Combined synopsis and solicitation, due August 27, 2026 at 2:00 PM EDT. Notice 5895ed8ef5244952aaeec88d443ef15a. https://sam.gov/workspace/contract/opp/5895ed8ef5244952aaeec88d443ef15a/view

## Points of contact

- Carrie Lawton, carrie.l.lawton.civ@army.mil, 7721065

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://abierto.us/opportunities/w911s226u3863.