# FY25: Lake Nona Medium Voltage Repair

Canonical: https://abierto.us/opportunities/36c24825q0885

- Solicitation number: 36C24825Q0885
- Notice type: Special notice
- Status: Closed. Deadline was June 16, 2025 at 11:00 AM EDT
- Department: Department of Veterans Affairs
- Contracting office: 248-Network Contract Office 8 (36C248)
- NAICS: 238210 Electrical Contractors and Other Wiring Installation Contractors
- Product or service code: J061 Maintenance, Repair and Rebuilding of Equipment: Electric Wire, and Power and Distribution Equipment
- First posted: June 13, 2025
- Last posted: June 13, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/e99b7a72f1b4431399cdd8438645d194/view

## Description

The Department of Veteran Affairs, Network Contracting Office 08 invites interested Contractors to attend a site visit for the purpose of assessing the issues identified in the government-generated Trouble Call report. This site visit will assist prospective offers in evaluating the work environment and technical requirements in preparation for submitting a quote under the upcoming Request for Quote (RFQ).

**Instructions:** Interested parties must pre-register attendees (no more than two) by providing names to Robert.edwards2@va.gov and rohan.mckenzie@va.gov no later than June 16, 2025, 11:00 AM. Please arrive on time and bring proper identification to gain access to the facility.

**Site Visit Details:**

**Date:**

**June 17, 2025 Time:** 10:00 AM (local time)

**Location:** Orlando VA Medical Center at Lake Nona, 13800 Veterans Way, Orlando, FL 32827 Meeting Point: Inside the lobby near the piano Purpose: Visual inspection and discussion of the issue described in Trouble Call Report Follow-up: Contractor questions will be address on-site and incorporated into the forthcoming RFQ as appropriate.

**Background:** Emergency (generator) power circuit(s) to the Lake Nona clinic are faulted and/or unreliable. The medium voltage circuit DAG-3 is the emergency (generator) circuit powering the Clinic substation SS-CG2; and is the alternate power source for Clinic substation SS-CG1. It was Hi-Pot tested and the report indicated a catastrophic failure on B-phase, requiring both substations to be placed on the alternate circuit (DAG-15) with no redundancy.

A visual inspection of manholes EA1-1 and EA1-2 in the duct bank series noted splices in them that show signs corrosion and degradation. Troubleshooting, testing was performed on the circuit and damage to the B-phase conductor insulation is suspected to be localized the within the ductwork itself requiring emergent replacement. The medium voltage circuit DAG-15 is the emergency (generator) circuit powering the Clinic substation SS-CG1 and is the alternate power source for Clinic substation SS-CG2.

It was Hi-Pot tested and the report indicated signs of leakage, likely from several splices/phases in the duct bank series manholes. A visual assessment was performed in conjunction with the Hi-Pot test and noted signs of swelling on several splices. Circuit DAG15 is the sole operable emergency (generator) circuit to the Clinic substations SS-CG1/2 (in its current switched state) and in urgent need of replacement and/or repair. The Normal power circuit to the Lake Nona Domiciliary is unreliable.

The medium voltage circuit DAN-2 is the sole normal power circuit powering the Domiciliary substation SS-DG1. It was quickly identified to have sustained a catastrophic splice failure on only C-phase on 12Nov24 in manhole NA2-5. Only C- phase splice was repaired, and the circuit was put back in service in >24hrs. During the visual assessment splices were noted in manholes NA2-5, NA2-6, NA2-7, and NA2-8 with various signs of corrosion and swelling indicative of impending failure.

Circuit DAN-2 requires urgent replacement. DBN-7 Hospital (Normal Power) circuit - A visual assessment confirmed smoke and electrical burning signs from manhole NB2-3 near the golf cart yard of the warehouse.Â Suspected leaking splice damage.Â IMG_1005 1.3gp.

**Attachments:** ATTACHMENT A - Trouble Call Report of the Hi-Pot Cable test DAG-3 ATTACHMENT B - Trouble Call Report of the Hi-Pot Cable test DAG-15 Note: This notice is for informational and planning purposes only. It does not constitute a solicitation or guarantee of future contract award.